Installation Recommendations
Installation Checklist
This checklist should be used to validate the completion
of a generator set installation, prior to commissioning.
A checklist should be completed for each generator of a
multiple installation.
Project Details
Project name
………………………………………………….......……...........
………………………………………………….......……………
Customer (End User)
………………………………………………….......……….......
………………………………………………….......……………
Address of Site
……………………………………………………………………
…..........................................................................................
……………………………………….......................................
Tel.No. …..…………………………………….......……………
Mobile …………………………………...................................
Email. ………..…………………………………......…………...
-------------------------------------------------------------------
Generator Set Details
Generator Set Model. ..………………………......…………...
Generator Set Serial No. ………..........................................
Set No..................................................................................
Controller Type ………………...............................................
Engine Sr. No. ……………………………………….......….....
A C Generator Sr. No. .....…………………………................
Controller Sr. No. ………………………................................
-------------------------------------------------------------------
Site Information – Yes or No
Site clean & clear from obstruction & secure......................
Site services complete & commissioned.............................
(lighting, auxiliary supply, water etc)
Installation - open air or closed room..................................
Installation on level & firm ground........................................
No loose material near generating set …………..................
Pipes & cables secured .......................................................
Air intake & exit paths clear & clean ...................................
Electrical bonding complete ………………………...............
Comments / Any other irregularity …………................……
..…………………………………………………..………………
……......................................................................................
-------------------------------------------------------------------
Cooling System – Yes or No
Radiator air outlet clean, free from obstruction ……......….
Coolant overflow well routed for spillage ……….............…
Possibility of hot air recirculation …………….....…......……
-------------------------------------------------------------------
Fuel System – Yes or No
Bulk storage tank installation complete ..............................
Transfer pump installed & connected ….......….……......….
Piping correct material, cleaned & leak-free …..............….
Spillage containment complete …...................................…
Vent installed, piped to safe area and open …....................
Day tank fill point clean & clear …….................……………
Electrical bonding completed ….............................………..
Storage facility secured ………........................……………..
-------------------------------------------------------------------
Exhaust System – Yes or No
Installation prevents exhaust recirculation …......….....……
Installation allows for pipework expansion ……............…..
Welded joints & flanges secured with gaskets ……......…..
Piping correctly supported …………………………......…....
Stack prevents rain ingress …………………..………......….
Condensate drain provided ……………..…………….......…
Exit directed away from building …….………………......….
System lagged & cladded properly ……………….......…….
Flammable material properly protected …………........……
-------------------------------------------------------------------
Ventilation – Yes or No
Installation prevents hot air recirculation …….............…….
Installation accounts for prevailing wind ......……….......….
Air exit directed away from building ….......……….......……
Forced ventilation if in place wired ……………...................
Moving Louvers if any connected to system …....…......….
Inlet, outlet & enclosure bird protected ……….............……
-------------------------------------------------------------------
Electrical System – Yes or No
Control system
Field wiring to set mounted control complete ...…......……
Customer wiring to control complete ……………............…
Interconnection to remote control complete ….............…..
Remote emergency stop controls wired ……….............…..
Generator / Switchgear / Changeover / transfer
Means of disconnection / isolation provided ........….......…
Switchgear installation & pre-testing complete ……...........
Cables installed correctly, marked & flexible ……...............
Power connections complete ……………........…….......…..
Enclosure penetration properly sealed …..........…….......…
Enclosure
All electrical boxes clean& covers replaced …..….......……
Auxiliary electrical supply complete ……...........….......……
Grounding system complete & tested ……….......…......….
Utility supply available as required …….............……......…
-------------------------------------------------------------------
Any other comment / observation if any
……………………………………………………………………
………………………................................………..............….
…………………………………………………….......…………
-------------------------------------------------------------------
Checklist completed by
……………………………………………………………….......
......…………………….................................…………………
Date ……………………………………………………........….
Company……........................................................……........
-------------------------------------------------------------------
Note : Completion of this checklist does not relieve
The Installer of contractual obligation.
-------------------------------------------------------------------