Earthing
A.The generating set should be connected to earth in
accordance with local regulations.
B.All metal-work of the generating set should be bonded
so that there is a continuous low impedance path from
all parts of it, including the engine and bed-plate, back
to the earth point.
C.The size of the cable used for the main earth
connection should be of adequate size.
D.If residual current protection is required for personnel
protection it should not be fitted to the generator circuit
breaker. This can cause spurious tripping, but should
be fitted to the sub circuits requiring the protection.
E. If residual current protection is fitted to the generator
circuit breaker, care should be taken for the earth cable
connection, as the connection point will determine
whether the generator windings and the load are
protected, or only the load is protected.
F. When fitting residual current protection care should
be taken to ensure that there is only ONE earth path to
the main earth point.
G.Earthing all metal-work WITHOUT connecting it to the
generator star point will not give earth protection for
the generator load.
H.If the generators are operating in parallel the star
points can be connected in parallel provided this does
not cause parallel paths for the earth protection, or
cause excessive circulating currents
I. The generating set and all associated equipment,
control and switch gear panels must be earthed before
the set is put into operation.
J. 4 numbers earth pits are required as per Indian
Electricity rules or local electricity board.
2 earthing pits for genset / control panel body
2 earthing pits for neutral
K. GI strips of suitable size may be used for earthing.
Earthing should be checked at earth strip and the
resistance should be less than 1 ohm. For gensets
with AVM’s between engine / alternator and base rail,
the earthing MUST be done at the engine / alternator
and NOT at base rail.
L. The neutral of the generator is not bonded to the
generator frame as supplied from the factory. An earth
terminal is provided inside the terminal box adjacent to
the main terminals. If the set is required to operate
with the neutral earthed, a substantial earth conductor
(normally equivalent to one half of the section of the
line conductors) must be connected between the
neutral and the earth terminal inside the terminal
box.Additional earth terminals are provided on the
generator feet.
Installation Recommendations
Electrical design
H.The terminal box is most conveniently glanded on
either right or left hand side. Both panels are
removable for drilling/punching to suit glands/or
glanding boxes. If single core cables are taken through
the terminal box side panel, an insulated or non-
magnetic gland plate should be fitted.
I. Incoming cables should be supported from either
below or above the box level and at a sufficient
distance from the centre line of the generating set.
This would avoid a tight radius at the point of entry into
the terminal box panel, and allow move ment of the
generator set on its anti-vibration mountings without
excessive stress on the cable. Before making
final connections, test the insulation resistance of the
windings. The AVR should be disconnected during
this test. When making
connections to the
terminals the
incoming cable
termination should be
placed on top of the
winding lead
termination/s and
clamped with the nut
provided.
J. Care to be taken, that weights of cables should not
fall on alternator / base rail. It is recommended to
support output cables on separate structure on ground.
K.External wirings, when provided for remote
voltage / excitation monitoring / droop CT etc. shall be
screened sheathed type. Maximum length of such
wiring should not exceed 5 meters.
L. Power cables should be type installed in a duct or a
cable tray.
Electrical design
Cable access from either side or
above
Overhead Cables